| Brand | Elektrogas |
|---|---|
| Model | LD & LDM Series |
| Specification | Technical Specifications • Voltage Options: 230V AC (50/60Hz), 110-120V AC (50/60Hz), 24V DC • Voltage Tolerance: -15% to +10% • Power Consumption: 10 VA (1W for 24V DC); Integrated valves: 2 × 21 VA • Operating Temperature: -15°C to +60°C • Max Working Pressure: 500 mbar (50 kPa) • Enclosure Protection: LD Series IP54, LDM Series IP65 • Cable Gland Options: PG9 (Ø6–8 mm), PG16 (Ø10–12 mm), ISO 4400 plug PG11 optional • Max Wire Cross-Section: 2.5 mm² • Replaceable Fuse: 5 A slow-acting • Output Signals: 5A max (resistive load), 2A max (inductive load) • Reset Mechanism: Mains voltage activation • Testing Configurations: Adjustable test period 10s–90s; Filling/Discharge time 3s • Connections: Rp 1/4 • Gas Compatibility: Non-aggressive gases (EN 437 Families 1, 2, 3) • Compliance: Integrated Pressure Switch EN 1854; Integrated Solenoid Valves EN 161 Class A • Weight: LD1 = 450 g; LDM2 = 1200 g; LD3 = 1600 g; LDM4 = 2100 g Key Features & Benefits |